|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
38.
|
What is the MAXIMUM balanced demand load, in VA, permitted to be connected to a new service of a commercial building where given the following conditions? I. The service is 208Y/120-volts, 3-phase, with a 600 ampere rated main circuit breaker. II. The maximum load must not exceed 80 percent of the ampere rating of the main circuit breaker.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
To solve this problem, apply the 3-phase power formula: P = I x E x 1.732, and multiply by 80%: P = 600 amperes x 208 volts x 1.732 x 80% = 172,923 VA
Incorrect answer. Please choose another answer.
|
|
|
|
|
|
|
|
|
|
|
48.
|
Given: A one-family dwelling to be built will have 4,000 sq. ft. of livable space, a 600 sq. ft. garage, a 400 sq. ft. open porch, a 2,000 sq. ft. unfinished basement (adaptable for future use), three (3) small-appliance branch-circuits and a branch circuit for the laundry room. Determine the demand load, in VA, on the ungrounded service-entrance conductors for the general lighting and receptacle loads using the standard method of calculation for a one-family dwelling.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
To solve this problem take into consideration the following related information regarding calculations for dwelling units: 1) According to Section 220.12, a unit load of 3 VA as specified in Table 220.12 shall constitute the minimum lighting load. The calculation floor area shall not include garages and open porches. 2) As per Section 220.52(A), each small appliance circuit shall be calculated at 1,500 VA each. 3) Section 220.52(B) specifies a load of not less than 1,500 VA is to be included for the laundry branch circuit. 4) As permitted by Section 220.42, the demand factors specified in Table 220.42 shall apply to that portion of the total branch circuit load calculated for general illumination. Therefore, to calculate the demand load do the math as follows. 4,000 sq. ft. + 2,000 sq. ft. = 6,000 sq. ft. x 3 VA = 18,000 VA three small appliance circuits @ 1,500 VA each = 4,500 VA one laundry circuit @ 1,500 VA = 1,500 VA Total connected load = 24,000 VA 1st 3,000 VA @ 100% 3,000 VA 24,000 VA - 3,000 VA = 21,000 VA (remainder) @ 35% = 7,350 VA Total demand load = 10,350 VA
Incorrect answer. Please choose another answer.
|
|
49.
|
Determine the MINIMUM size Type SOW flexible cord that may be used to supply a 30 hp, 3-phase, 480-volt, continuous-duty, ac motor from the motor controller to the motor terminations. Assume voltage-drop and elevated ambient temperature are not considerations.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
In compliance with Section 430.6, where flexible cord is used to supply motors, the size of the conductors shall be selected in accordance with Section 400.5. For general motor applications, Section 430.6(A)(1) indicates the full-load current values given in Table 430.250 are to be used where sizing the conductors for a 3- phase ac motor. Section 430.22 requires conductors that supply a single motor used in a continuous duty application shall have an ampacity of not less than 125% of the motor full-load current rating. Locate the FLC of the motor, 40 amperes, as shown in Table 430.250, then as per Section 430.22 multiply by 125% to determine the required ampacity of the conductors to supply the motor. FLC of 30 hp motor = 40 amperes x 125% = 50 amperes Size 4 AWG SOW cord with an allowable ampacity of 60 amperes should be selected from Column A of Table 400.5(A)(1).
Incorrect answer. Please choose another answer.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
62.
|
Where a mobile home park has 25 mobile home lots calculated at 15,000 VA each, determine the MINIMUM required ampacity required for the ungrounded service-entrance conductors.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
As required by Section 550.30, the secondary distribution system for a mobile home lot is to be single-phase, 120/240-volts. Section 550.31(1), mandates each mobile home lot is to be calculated at a minimum of 16,000 VA; this is the value to be used for this calculation. A demand factor of 24% is permitted to be applied as shown in Table 550.31. First determine the demand load: 25 lots x 16,000 VA (minimum) = 400,000VA "‹ X .24 (demand factor) 96,000 VA (demand load) Next determine the load in amperes: I = power I = 96,000 VA = 400 amperes volts 240 volts
Incorrect answer. Please choose another answer.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
78.
|
A twelve (12) unit apartment building will have a 5,500 watt electric clothes dryer placed in each apartment. Apply the general method of calculation and determine the demand load, in VA, on the ungrounded service-entrance conductors for the dryers.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Use Table 220.54 and first find the demand factor, in percent, for 12 dryers: 47% - 1% (minus 1% for each dryer exceeding 11) = 46% demand factor 12 dryers x 5,500 watts = 66,000 VA (connected load) x 46% = 30,360 VA demand
Incorrect answer. Please choose another answer.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
92.
|
Where an apartment complex has a calculated connected lighting load of 205.4 kVA, what is the demand load, in kVA, on the ungrounded service-entrance conductors where applying the standard (general) method of calculation? Given: Each dwelling unit in the complex has cooking facilities provided.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The demand factors specified in Table 220.42 may be applied to calculate the general lighting demand loads for dwelling units. First, convert into VA: 205.4 kVA x 1,000 = 205,400 VA Next, apply the values given in Table 220.42: first 3,000 VA @ 100% = 3,000 VA 3,001 to 120,000 VA @ 35% = 117,000 VA @ 35% = 40,950 VA remainder 205,400 VA - 120,000 VA = 85,400 VA @ 25% = 21,350 VA Demand = 65,300 VA Finally, determine the kVA: 65,300 VA = 65.3 kVA 1,000
Incorrect answer. Please choose another answer.
|
|
|
|
95.
|
When supplying a 36,000 VA, 240-volt, single-phase load in an area where the ambient temperature reaches 119F, determine the MINIMUM size 75C rated copper conductors required to supply the load.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
First, apply the single-phase current formula to determine the load in amperes: I = power I = 36,000 VA = 150 amperes load volts 240 volts Next, due the elevated temperature, divide the load of 150 amperes by .75, the temperature correction factor given in Table 310.15(B)(2)(a): required ampacity = 150 amperes = 200 amperes .75 Then, size 3/0 AWG 75C copper conductors with an allowable ampacity of 200 amperes should be selected from Table 310.15(B)(16).
Incorrect answer. Please choose another answer.
|
|
|
|
|
|
|